Smoke Vent with Roof Access and Daily Ventilation EN12101-2

Surespan thermally broken aluminium SRHP/AOV 140° smoke vent roof hatch designed to EN12101-2. The AOV also offers push button comfort (daily) air ventilation.

The lid and upstand features a 50mm thermally broken section and fully insulated with 50mm CFC and HCFC free Polyisocyanurate insulation (0.43 W/m²K). Alternative non-combustible Mineral Wool insulation can be specified at no extra cost. (0.63 W/m²K)

The Smoke vent comes with a 300mm insulated upstand and is fitted with an aluminium curb liner as standard.

GUIDE SPECIFICATION
Fully Certified to EN12101-2 and CE Marked.
• Material: Aluminium with 50mm thermal break.
• Cover: 50mm (2”) fully insulated kerb and lid, corner welded and reinforced. Aluminium wind deflectors.
• Curb: 300mm (12”) in height with external curb liner, 50mm thermal break and 50mm polyisocyanurate insulation to 0.43 W/m2K U-value. Alternative 50 mm mineral wool insulation at no extra cost (0.63 W/m2K).
• Seal: Double unbroken bubble & blade seal to lid
• Operation: 24VDC/4A Actuator tested 10,000 opening and 1,000 comfort ventilation according to EN12101-2.
• Hinges: Heavy duty continuous hidden hinge
• Finish: Mill finish aluminium, Single or two colour powder coating optional.

Specification Details

Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Surespan Limited is consulted before specifying.

Surespan Limited
Leamore Close
Walsall
United Kingdom
WS2 7NL
P: 01922711185

Smoke Vent with Roof Access and Daily Ventilation EN12101-2

Standard
• Area: 1.5 m2
• Height: 300 mm
• Length: 1050 mm
• Width: 1550 mm
• Material: Aluminium
• Snow Load: 500 N/m2
• U-value (overall): 0.43 W/m2k
• CE Marking: Yes
• Typical Use: Smoke Vent
• Uniclass: Pr_70_65_04_56 Natural smoke and heat exhaust ventilators

1m2 Airflow 1050 x 1050
• Area: 1 m2
• Height: 300 mm
• Length: 1050 mm
• Width: 1050 mm
• Material: Aluminium
• Snow Load: 500 N/m2
• U-value (overall): 0.43 W/m2k
• CE Marking: Yes
• Typical Use: Corridors, Daily Ventilation, Roof Access, Smoke Vent, Stairwells
• Uniclass: Pr_70_65_04_56 Natural smoke and heat exhaust ventilators

1.5m2 Airflow 1260 x 1260
• Area: 1.5 m2
• Height: 300 mm
• Length: 1260 mm
• Width: 1260 mm
• Material: Aluminium
• Snow Load: 500 N/m2
• U-value (overall): 0.43 W/m2k
• CE Marking: Yes
• Typical Use: Corridors, Daily Ventilation, Roof Access, Smoke Vent, Stairwells
• Uniclass: Pr_70_65_04_56 Natural smoke and heat exhaust ventilators

File Downloads