Tap offs are colour coded and non-interchangeable between busbar types. The slide locking, positive latching tap off plug prevents accidental disconnection and can be added to or removed from the busbar while the system is live. All 3 metre, 32 Amp tap offs incorporate an unfused plug, and as standard, 16mmØ metal flexible conduit enclosing 3 metres of 4mm2 Cables. These units are designed to comply with Regulation 434.2.1 of BS 7671:2008 Amd 3. 5 metre unfused tap offs are also available for use with individual track runs that are rated at no more than 32Amp, where the protection of the tap off against both overload and fault current is provided by the track protective device.
CMD tap off units conform to the high integrity protective requirement by virtue of using a protective conductor of 4mm enclosed within a flexible conduit, thus providing additional protection against mechanical damage.
FEATURES AND BENEFITS
Choice: a comprehensive range of supply versions
Flexibility: can be used in new or existing layouts
Safety: all units are designed to comply with regulation 434.2.1 of BS 7671: 2008
Convenience: all tap offs are colour coded & non-interchangeable with slide locking and positive latching to prevent accidental disconnection
Only suitable for use with Betatrack busbar systems
Complies with regulation 434.2.1 of BS 7671: 2001 Amd 3
Available in Standard Earth, Clean Earth (Low Noise), Dual Circuit, Auxiliary Earth & 3 Phase
Can be added or disconnected from Betatrak busbar while live
Colour coded for convenience
32 AMP 3 METRE TAP OFF
All 3 metre long, 32A tap-offs incorporate an unfused plug, and as standard, 16mmØ metal flexible conduit enclosing 3 metres of 4mm2 cables.
These units are designed to comply with Regulation 434.2.1 of BS 7671:2008.
32 AMP 5 METRE TAP OFF
5-metre unfused tap-offs are also available for use with individual track runs that are rated at no more than 32A, where the protection of the tap-off against both overload and fault current is provided by the track protective device
CMD tap off units conforms to the high integrity protective requirement by virtue of using a protective conductor of 4mm enclosed within a flexible conduit, thus providing additional protection against mechanical damage.
The flexible conduit is supplied 225mm shorter than the specified tap-off length to allow compliance with 434.2.1.
All 13A fused tap-offs are fitted with 4mm high integrity earth conductor.
Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that CMD Ltd is consulted before specifying.
|
|
||
| Fitting Options (?) | Underfloor | |
| Product Type (?) | Standard Earth - 63 Amp | |
|
|
||
| Features (?) | Auxiliary Earth & 3 Phase , Available in Standard Earth , Clean Earth (Low Noise) , Colour coded for convenience , Dual Circuit | |