Thermostatic diverting valve with thermal disinfection The unique manual override function allows thermal disinfection against Legionella to be performed using the special tool. The special tool lifts the spindle, by-passing the operation of the thermostatic cartridge. The higher temperature hot water passes through the valve and pipework to thermally disinfect it.
Using the special tool and the manual override function allows thermal disinfection to be performed through to the outlets, so a complete flush can be performed not just a partial flush. Thermal disinfection helps protect the system against Legionella and other microbial organisms.
Specification
Max. working pressure: 10 bar - Static
Min. working pressure: 0.2 Bar : Dynamic
Max. inlet temperature: 85C
Inlet temperature range:
- hot supply: 55 - 65C
- cold supply: 0.5 - 20C
D 08 working pressure:
- low pressure: 0.2 - 1.0 Bar
- high pressure: 1.0 - 5.0 Bar
Max. inlet pressure ratio (H/C or C/H): 5:1
Accuracy: 2C
Setting Range: 30 to 50C
Min. temperature difference between inlet hot water and outlet mixed water: 10C
Min. flow for stable operation 4 l/m
Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Altecnic is consulted before specifying.
|
|
||
| Max Pressure (bar) (?) | 10 bar | |
| Max Static Pressure (?) | 10 bar | |
| Temperature (?) | 85 °C | |
|
|
||
| Material (?) | DZR Chrome Plated , EPDM , Stainless steel | |
|
|
||
| Connection Type (?) | Universal tailpiece with adaptor | |
|
|
||
| Uniclass (?) | Pr_65_54 Valve products | |