Mixcal Careflo Plus TMV

Thermostatic diverting valve with thermal disinfection The unique manual override function allows thermal disinfection against Legionella to be performed using the special tool. The special tool lifts the spindle, by-passing the operation of the thermostatic cartridge. The higher temperature hot water passes through the valve and pipework to thermally disinfect it.

Using the special tool and the manual override function allows thermal disinfection to be performed through to the outlets, so a complete flush can be performed not just a partial flush. Thermal disinfection helps protect the system against Legionella and other microbial organisms.

Specification

Max. working pressure: 10 bar - Static

Min. working pressure: 0.2 Bar : Dynamic

Max. inlet temperature: 85C

Inlet temperature range:

- hot supply: 55 - 65C

- cold supply: 0.5 - 20C

D 08 working pressure:

- low pressure: 0.2 - 1.0 Bar

- high pressure: 1.0 - 5.0 Bar

Max. inlet pressure ratio (H/C or C/H): 5:1

Accuracy: 2C

Setting Range: 30 to 50C

Min. temperature difference between inlet hot water and outlet mixed water: 10C

Min. flow for stable operation 4 l/m

Specification Details

Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Altecnic is consulted before specifying.

Altecnic
Mustang Drive
Stafford, Staffordshire
United Kingdom
ST16 1GW
P: +44 (0)1785 218200

Mixcal Careflo Plus TMV

Mixcal Careflo Plus 101-3001 15/22mm
• Max Pressure (bar): 10 bar
• Max Static Pressure: 10 bar
• Temperature: 85 °C
• Material: DZR Chrome Plated, EPDM, Stainless steel
• Connection Type: Universal tailpiece with adaptor
• Uniclass: Pr_65_54 Valve products

Mixcal Careflo Plus 101-3002 15/22mm
• Max Pressure (bar): 10 bar
• Max Static Pressure: 10 bar
• Temperature: 85 °C
• Material: DZR Chrome Plated, EPDM, Stainless steel
• Connection Type: Universial MX end with adaptor
• Uniclass: Pr_65_54 Valve products