SPECIFICATION
The Altecnic thermostatic regulator for domestic hot water re-circulation systems automatically maintains the specified water temperature.
The regulator controls the flow rate in accordance with the inlet water temperature by means of a dedicated internal thermostatic cartridge.
When the water temperature approaches the set value, the obturator progressively close and reduces the flow passage reducing the amount of water re-circulating.
The water supplied by the re-circulation pump is available to be distributed to other branches in the system, resulting in effective automatic thermal balancing.
Temperature gauge available.
Insulation shell available upon request
Medium: Potable water
Kv maximum: 1.8 m3/h
Kv disinfection: 1.0 m3/h
Kv min at 58C (DN 15): 0.10 20% m3/h
Kv min at 58C (DN 20): 0.12 20% m3/h
Kv (Dt = 5K): 0.45 m3/h
Max. working pressure: 16 bar
Max. differential pressure: 1 bar
Temperature adjustment range: 35 to 60C
Factory setting: 52C
Disinfection temperature: 70C
Closing temperature: 75C
Connections - or female: BS EN 10226-1
Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Altecnic is consulted before specifying.
|
|
||
| Finish(es) (?) | Brass | |
| Material (?) | ABS Polymer , DZR Brass Alloy , Elastomer , PSU , Stainless Steel | |
|
|
||
| Product ID Number (?) | 116140 | |
|
|
||
| Uniclass (?) | Pr_65_54 Valve products | |
|
|
||
| Max Pressure (bar) (?) | 16 bar | |
| Temperature (?) | 35 - 60 °C | |
|
|
||
| Connection Type (?) | Female BSP | |